UPS maintenance checklist

Read the UPS display every day and confirm it is not on bypass. Each month, record battery float voltage and inspect every cell. Each quarter, trend cell impedance. Every year, run a full preventive maintenance visit, an infrared scan and a transfer test. Eaton, APC and Vertiv put VRLA battery life at 3 to 5 years. Fill in the checklist below, then download it as a PDF (filled or blank) or an Excel file. Morsa asks for each check and flags a missed or failed one.

Updated November 12, 2026

Equipment and technician
Optional
Optional
Daily checks (4)
1.Read the display: normal mode, not on bypass, no active alarm; note anything else
Read the display: normal mode, not on bypass, no active alarm; note anything else
2.Record load, input and output voltage and battery status from the display or monitoring
Record load, input and output voltage and battery status from the display or monitoring
3.Check the UPS and battery room temperature is within 20 to 25 C (68 to 77 F)
Check the UPS and battery room temperature is within 20 to 25 C (68 to 77 F)
4.Look and listen for fan noise, heat, odors or visible damage
Look and listen for fan noise, heat, odors or visible damage
0 of 4 marked
Your own tasks (0)

Add tasks your site needs. They print with this checklist, on the full schedule and in Excel. 0 on this checklist, 0 of 15 used across the UPS checklists.

Before you file it: 3 to fix
  • FixAdd the UPS number, so the check is filed against the right UPS.
  • FixAdd the technician's name.
  • FixAdd the date.
  • Check4 of 4 checks are not marked yet.
Show
UPS maintenance checklistDaily checksOnline UPS with VRLA batteries. Lithium and flooded batteries: the maker's manual wins.UPS numberLocationDateTechnicianCompany or siteReviewed byMark each check Done, Issue or N/A; a check with no N/A box applies to every unit. Write what is wrong against each issue and open a work order. Sourcenumbers refer to the list at the end.#Daily checksSourceDoneIssueN/AReading or note1Read the display: normal mode, not on bypass, no active alarm; noteanything else12Record load, input and output voltage and battery status from thedisplay or monitoring13Check the UPS and battery room temperature is within 20 to 25 C (68to 77 F)34Look and listen for fan noise, heat, odors or visible damage1Technician signatureWork orders openedReviewed by (maintenance lead)DateBased on:1. Eaton, Data center downtime: risk and cost avoidance through service (read 12 November 2026)2. Eaton, UPS lifecycle maintenance schedule, SER110FXA, August 2026 (read 12 November 2026)3. Schneider Electric (APC), What is the expected life of my APC UPS VRLA battery? (read 12 November 2026)4. Vertiv, UPS FAQ and capacitor and fan replacement data sheet (read 12 November 2026)5. Ametek (ATEcorp), Battery testing guide, summarizing IEEE 1188 (read 12 November 2026)6. Eagle Eye Power Solutions, Battery inspection, maintenance and testing (read 12 November 2026)7. Fluke, Recommended battery tests and testing schedule for battery back-up systems (read 12 November 2026)UPS maintenance checklist: Daily checks.

Next, Morsa schedules this checklist, asks the technician for it from their phone, logs the result against the asset and flags any check that is missed or fails. Size a UPS with the kVA calculator or book a demo.

Blank UPS forms to print:

1 page, letter size. 0 of 4 checks marked.

Runs in your browser. Nothing you type is uploaded; the check is saved only in this browser, and the PDF and Excel files are built on your device.

UPS maintenance schedule at a glance

How oftenWhat to checkSource
DailyDisplay, bypass status, load, room temperatureEaton, APC
MonthlyFloat voltage and current, visual inspection of every cell, air filtersIEEE 1188 summaries, Eaton
Every 3 monthsCell voltages, impedance or conductance, terminal temperaturesIEEE 1188 summaries
Every 6 monthsFull battery inspectionEaton
YearlyPM visit, infrared scan, transfer test, connection resistance, capacitors and fansEaton, IEEE 1188 summaries
3 to 5 yearsReplace VRLA batteriesEaton, APC, Vertiv

We did not read IEEE 1188 or IEEE 450 themselves. The battery intervals here come from Ametek, Eagle Eye Power Solutions and Fluke, which summarize them.

How to use the UPS maintenance checklist

  1. Enter the UPS number and where it is.

  2. Pick the checklist that is due and mark each check Done, Issue or N/A. The display, bypass and battery checks cannot be marked N/A.

  3. Write the readings and what is wrong against failed items.

  4. Download the PDF (filled or blank) or the Excel file for the battery log.

UPS battery maintenance: the tests and the limits

TestIntervalLimit
Float voltage, charger output, temperatureMonthlyCompare with the maker’s float voltage
Cell impedance or conductanceQuarterlyResistance up 20% or more from baseline is a failure sign
Connection resistanceYearlyOver 20% above baseline: clean and retorque
Capacity (discharge) testAt least every 2 years or at 25% of expected life, whichever is soonerYearly once capacity drops 10% or life reaches 85%
Replace the batteryWhen capacity is below 80%Healthy is above 90% of rating

From summaries of IEEE 1188 (Ametek, Eagle Eye Power Solutions, Fluke). Capacity is a share of the manufacturer’s rating.

What the manufacturers say about UPS maintenance

  • Eaton: annual preventive maintenance; inspect VRLA batteries every 6 months and replace at 3 to 5 years, flooded at 12 to 15; inspect capacitors yearly and replace at 5 to 7; verify fans yearly and replace at 7; inspect air filters monthly.

  • Schneider Electric (APC): most batteries last 3 to 5 years; keep the room at 20 to 25 C because every 8 C rise halves battery life; run runtime calibrations once or twice a year at most.

  • Vertiv: VRLA batteries 3 to 5 years at 20 to 25 C, lithium-ion about 10 years; fans at 5 to 6 years and capacitors at 6 or 12 to 15 years, by model.

  • NFPA 70B: FLIR’s summary says the 2023 edition calls for inspecting all electrical equipment at least every 12 months. We did not read the standard itself.

Lithium UPS and the maintenance bypass

Lithium-ion batteries last longer and tolerate heat better, about 10 years up to 25 C against 3 to 5 for VRLA, per Vertiv, but they have their own service schedule. Follow the maker’s. For the maintenance bypass, do not improvise: use the manufacturer’s transfer procedure, and note Eaton’s warning that a UPS that has slipped onto bypass can look fine for months. That is why the daily check reads the bypass status.

Where the UPS sources disagree

Vertiv’s fan replacement is 5 to 6 years, Eaton’s is 7. Vertiv’s capacitor replacement is 6 or 12 to 15 years by model, Eaton’s 5 to 7 years on a generic list. Use your manual, and the shorter figure if it is unclear.

What to do when a UPS check fails

  • On bypass or an active alarm: treat the load as unprotected. Call your service provider and follow the manual’s procedure.

  • A swollen jar, leak or high-impedance cell: flag it for replacement and tell the provider.

  • Capacity below 80%: replace the string.

  • Write the reading on the checklist and open a work order. See the work order template.

UPS maintenance mistakes

  1. Never reading the display. A unit on bypass can look fine for months.

  2. Running runtime calibrations too often. APC says once or twice a year at most, because more shortens battery life.

  3. Running the room hot. Every 8 C halves VRLA life.

  4. No baseline. The 20% limits need a baseline from when the battery was new.

  5. Replacing on age alone. Capacity and impedance trends say when.

Keeping the UPS checks on schedule

Morsa asks for the daily display reading and the monthly battery log in WhatsApp, Teams, text or email and files them against the UPS. It compares impedance and float readings with your baseline, tells the maintenance lead about a unit on bypass or a drifting cell, and schedules the annual visit and the battery replacement date for approval.

Other maintenance checklists

Frequently asked questions

How often should a UPS be serviced?

Eaton recommends annual preventive maintenance and a semiannual battery inspection. The checklist adds daily and monthly checks.

How often should UPS batteries be replaced?

VRLA batteries every 3 to 5 years (Eaton, APC, Vertiv), sooner if capacity falls below 80% of rating or the room runs hot.

What is lithium UPS maintenance?

Lithium-ion batteries last about 10 years up to 25 C, per Vertiv. Follow the maker’s schedule; the VRLA tests do not all apply.

What is a UPS maintenance bypass switch?

It routes power around the UPS so it can be serviced. Use the manufacturer’s transfer procedure and confirm the bypass status afterwards.

What does a UPS preventive maintenance visit include?

Per Eaton: inspection, testing, calibration, updates, cleaning and a thermal scan of connections, plus firmware and field service bulletins.

What is IEEE 1188?

The recommended practice for maintaining and testing VRLA batteries. We cite its intervals from published summaries, not the standard itself.

Where Morsa fits

Know the UPS is on line, not on bypass.

Morsa asks for the readings, compares them with your baseline and flags a missed check, a unit on bypass or a drifting cell. It works in whatever your team runs on: WhatsApp, Teams, email or text.

Machines, people, and vendors, finally in one. We start with yours.

For queries, feedback or suggestions

© 2026 Morsa. All Rights Reserved. A Product by Lunar.

Machines, people, and vendors, finally in one. We start with yours.

For queries, feedback or suggestions

© 2026 Morsa. All Rights Reserved. A Product by Lunar.

Machines, people, and vendors, finally in one. We start with yours.

For queries, feedback or suggestions

© 2026 Morsa. All Rights Reserved. A Product by Lunar.