Free tool
Chiller maintenance checklist
Log the operating readings every day and compare condenser approach with the new-unit baseline. Check refrigerant and oil weekly, safety controls and leaks monthly, and clean the condenser tubes yearly. Test the tubes by eddy current every 2 to 5 years. Fill in the checklist below, then download it as a PDF (filled or blank) or an Excel file. The intervals are York’s and Daikin’s for water-cooled centrifugal chillers; for other types, use your manual. Morsa asks for the log and flags a missed or failed check.
Updated November 12, 2026
Chiller maintenance schedule at a glance
| How often | What to check | Source |
|---|---|---|
| Daily | Log readings, oil level, approach, discharge temperature | York YK guide |
| Weekly | Refrigerant charge, leak test, water quality, oil appearance, log trends | York (charge); Daikin and DOE (the rest) |
| Monthly | Oil return, starter, safety controls, water flows, full leak check | York YK guide |
| Every 3 months | Protective controls, contactors, superheat, infrared scan | Daikin IOM 1281-2 |
| Yearly | Clean condenser tubes, oil analysis, megger, vibration, calibration | York, Daikin |
| 2 to 5 years | Eddy current test of the tubes, relief valves | York, Daikin |
Both manufacturers’ lists are for water-cooled centrifugal chillers. Use the manual for your make and model.
How to use the chiller maintenance checklist
Enter the chiller number and the run hours.
Pick the checklist that is due and mark each check Done, Issue or N/A. Log, oil, leak and safety checks cannot be marked N/A.
Write the readings and what is wrong against failed items.
Download the PDF (filled or blank) for the plant room, or the Excel file for the log.
Chiller approach temperature: the number to log
Condenser approach is the refrigerant’s condensing (saturation) temperature minus the leaving condenser water temperature. As scale or sludge builds on the tube walls, it grows. The manufacturers give different triggers, so log it against a baseline from when the chiller was new or just cleaned.
| Source | Signal | What it means |
|---|---|---|
| York (Johnson Controls), daily | More than 4 F above the new-unit value | Check for dirty tubes |
| York, annual cleaning | 5 to 6 F above the new-unit value | Tubes need cleaning |
| Daikin Applied, monthly | Rise of 2 F or more | Excessive tube fouling may be present |
F is degrees Fahrenheit. Daikin notes its high-efficiency exchangers are designed for approaches of about 1 to 1.5 F. Take a baseline at start-up.
Refrigerant leak checks and EPA rules
Which rule applies. EPA’s Section 608 leak repair rule covers appliances with 50 or more pounds of ozone-depleting refrigerant. Its AIM Act rule, in force since January 1, 2026, covers appliances with 15 or more pounds of an HFC or a substitute with a GWP above 53. Residential and light commercial A/C is excluded.
The trigger. EPA lists chillers as comfort cooling, with a 10% leak rate over 12 months. Industrial process refrigeration is 30%.
Chillers are covered. EPA’s fact sheet says chillers fall under their own subsector, not the excluded residential and light commercial group.
The clock. Repair within 30 days (120 if an industrial process shutdown is required), then run initial and follow-up verification tests. Repairs must be done by a certified technician.
The math. Calculate the leak rate every time refrigerant is added. Under the AIM Act, comfort cooling chillers over the rate need a leak inspection once a year until a year passes without exceeding it.
If you will not repair. A retrofit or retirement plan is due within 30 days, to be finished within a year, and records are kept for three years.
Read the rule itself. EPA’s pages say to consult 40 CFR Part 82 Subpart F and 40 CFR 84.106. This is not legal advice.
Condenser tube cleaning and eddy current testing
York says to clean the condenser tubes annually, or earlier if conditions warrant, and gives eddy current testing at 2 to 5 years. Daikin gives 5 years. York’s guide says to brush-clean before any acid cleaning, never to use a steel bristle brush, and that acid cleaning must be done by an expert. York says evaporator tubes do not normally need cleaning, and Daikin says evaporators in treated closed circuits are not normally subject to fouling.
Where the chiller sources disagree
York puts the full leak check monthly, Daikin and the DOE guide weekly. York flags fouling at 4 F above the new-unit approach, Daikin at 2 F. The DOE guide says to inspect the chiller as the manufacturer recommends, typically at least quarterly. The daily item uses York’s 4 F; the monthly calculation uses Daikin’s 2 F. Carrier, Trane and other makes have their own schedules, which we did not read.
What to do when a chiller check fails
Safety control fails or oil is low: stop and lock out. Check the oil return system and filter drier before restarting.
Isolate before service. OSHA 29 CFR 1910.147 requires isolating the chiller and verifying isolation first.
Refrigerant loss: a certified technician finds and repairs the leak. Record the amount added.
Write the reading on the checklist, tell the maintenance lead and open a work order. See the work order template.
Chiller maintenance mistakes
No baseline. Without the new-unit approach, a rising number means nothing.
No refrigerant record. Leak rate depends on knowing what was added.
Untested safety controls. They only matter on the day they trip.
Cleaning only when it fails. Annual cleaning is the York interval.
Logs kept but never read. Review the weekly trend.
Keeping the chiller log on schedule
Morsa asks the operator for the daily log reading by phone, in WhatsApp, Teams, text or email, and files it against the chiller. It compares condenser approach with the baseline you set and tells the maintenance lead when it drifts. Refrigerant additions are logged as they happen and the leak rate is kept current, and weekly, monthly and annual tasks are scheduled for approval.
Other maintenance checklists
Preventive maintenance checklist: the hub, a general PM checklist for any machine
Cooling tower maintenance checklist: the water side of the condenser loop
Commercial HVAC maintenance checklist: rooftop units and air handlers
UPS maintenance checklist: for data centers, the power behind the cooling
Generator maintenance checklist: standby power tests
Frequently asked questions
How often should a chiller be serviced?
Log daily, check refrigerant and oil weekly, safety controls and leaks monthly, clean the condenser tubes yearly. The DOE guide adds a manufacturer inspection at least quarterly.
What is on a commercial chiller maintenance checklist?
Logs, oil, refrigerant, leaks, approach, safety controls, starter, tube cleaning, oil analysis, vibration and eddy current testing.
What is a York chiller maintenance schedule?
Johnson Controls lists daily, weekly, monthly and yearly items plus eddy current testing every 2 to 5 years. The checklist follows it.
How often should a chiller be checked for refrigerant leaks?
York says monthly, Daikin and DOE weekly. EPA’s rules set a 10% leak rate for comfort cooling chillers and require repair within 30 days.
How often should chiller tubes be cleaned?
Condenser tubes yearly, or sooner if approach rises 5 to 6 F over the new-unit value (York). Evaporator tubes rarely need it.
What is eddy current testing on a chiller?
A test of the tube walls to measure thickness. York recommends it every 2 to 5 years.
Related tools
Sources
Daikin Applied, IOM 1281-2 Centrifugal Water Chillers (read November 12, 2026)
US DOE FEMP, O&M Best Practices Guide, Release 3.0 (read November 12, 2026)
EPA, Stationary refrigeration leak repair requirements (read November 12, 2026)
OSHA, 29 CFR 1910.147, The control of hazardous energy, osha.gov (read November 12, 2026)