Log the operating readings every day and compare condenser approach with the new-unit baseline. Check refrigerant and oil weekly, safety controls and leaks monthly, and clean the condenser tubes yearly. Test the tubes by eddy current every 2 to 5 years. Fill in the checklist below, then download it as a PDF (filled or blank) or an Excel file. The intervals are York’s and Daikin’s for water-cooled centrifugal chillers; for other types, use your manual. Morsa asks for the log and flags a missed or failed check.

Updated November 12, 2026

Equipment and technician
Optional
Optional
Daily checks (8)
1.Record operating conditions on the log sheet: pressures, temperatures, motor current
Record operating conditions on the log sheet: pressures, temperatures, motor current
2.Check the oil level in the reservoir is within the marked operating range
Check the oil level in the reservoir is within the marked operating range
3.Read the control display for status and error messages
Read the control display for status and error messages
4.Check entering and leaving chilled liquid and condenser water temperatures and pressures
Check entering and leaving chilled liquid and condenser water temperatures and pressures
5.Compare condenser approach with the new-unit baseline; over 4 F above it points to fouled tubes
Compare condenser approach with the new-unit baseline; over 4 F above it points to fouled tubes
6.Read compressor discharge temperature; York YK normal operation stays under 220 F (104 C)
Read compressor discharge temperature; York YK normal operation stays under 220 F (104 C)
7.Check all setpoints are set and working as intended
Check all setpoints are set and working as intended
8.Walk the plant room for leaks, odors, noise and housekeeping
Walk the plant room for leaks, odors, noise and housekeeping
0 of 8 marked
Your own tasks (0)

Add tasks your site needs. They print with this checklist, on the full schedule and in Excel. 0 on this checklist, 0 of 15 used across the chiller checklists.

Before you file it: 3 to fix
  • FixAdd the chiller number, so the check is filed against the right chiller.
  • FixAdd the technician's name.
  • FixAdd the date.
  • Check8 of 8 checks are not marked yet.
Show
Chiller maintenance checklistDaily checksWater-cooled centrifugal chiller (York, Daikin). Air-cooled and screw units: the maker's manual wins.Chiller numberLocationRun hoursDateTechnicianCompany or siteReviewed byMark each check Done, Issue or N/A; a check with no N/A box applies to every unit. Write what is wrong against each issue and open a work order. Sourcenumbers refer to the list at the end.#Daily checksSourceDoneIssueN/AReading or note1Record operating conditions on the log sheet: pressures, temperatures,motor current12Check the oil level in the reservoir is within the marked operating range13Read the control display for status and error messages14Check entering and leaving chilled liquid and condenser watertemperatures and pressures15Compare condenser approach with the new-unit baseline; over 4 Fabove it points to fouled tubes16Read compressor discharge temperature; York YK normal operationstays under 220 F (104 C)17Check all setpoints are set and working as intended38Walk the plant room for leaks, odors, noise and housekeeping3Technician signatureWork orders openedReviewed by (maintenance lead)DateBased on:1. Johnson Controls (York), YK-CP with OptiView Control Center Operation and Maintenance Guide, Form 160.96-O1, Nov 2025 (read 12 November 2026)2. Daikin Applied, IOM 1281-2 Centrifugal Water Chillers, maintenance schedule (read 12 November 2026)3. US DOE FEMP, O&M Best Practices Guide, Release 3.0, section 7.4.8 Chillers checklist (read 12 November 2026)4. EPA, AIM Act leak repair requirements for appliances containing HFCs, fact sheet, January 2026 (read 12 November 2026)Chiller maintenance checklist: Daily checks.

Next, Morsa schedules this checklist, asks the technician for it from their phone, logs the result against the asset and flags any check that is missed or fails. See data center equipment lead times or book a demo.

Blank chiller forms to print:

1 page, letter size. 0 of 8 checks marked.

Runs in your browser. Nothing you type is uploaded; the check is saved only in this browser, and the PDF and Excel files are built on your device.

Chiller maintenance schedule at a glance

How oftenWhat to checkSource
DailyLog readings, oil level, approach, discharge temperatureYork YK guide
WeeklyRefrigerant charge, leak test, water quality, oil appearance, log trendsYork (charge); Daikin and DOE (the rest)
MonthlyOil return, starter, safety controls, water flows, full leak checkYork YK guide
Every 3 monthsProtective controls, contactors, superheat, infrared scanDaikin IOM 1281-2
YearlyClean condenser tubes, oil analysis, megger, vibration, calibrationYork, Daikin
2 to 5 yearsEddy current test of the tubes, relief valvesYork, Daikin

Both manufacturers’ lists are for water-cooled centrifugal chillers. Use the manual for your make and model.

How to use the chiller maintenance checklist

  1. Enter the chiller number and the run hours.

  2. Pick the checklist that is due and mark each check Done, Issue or N/A. Log, oil, leak and safety checks cannot be marked N/A.

  3. Write the readings and what is wrong against failed items.

  4. Download the PDF (filled or blank) for the plant room, or the Excel file for the log.

Chiller approach temperature: the number to log

Condenser approach is the refrigerant’s condensing (saturation) temperature minus the leaving condenser water temperature. As scale or sludge builds on the tube walls, it grows. The manufacturers give different triggers, so log it against a baseline from when the chiller was new or just cleaned.

SourceSignalWhat it means
York (Johnson Controls), dailyMore than 4 F above the new-unit valueCheck for dirty tubes
York, annual cleaning5 to 6 F above the new-unit valueTubes need cleaning
Daikin Applied, monthlyRise of 2 F or moreExcessive tube fouling may be present

F is degrees Fahrenheit. Daikin notes its high-efficiency exchangers are designed for approaches of about 1 to 1.5 F. Take a baseline at start-up.

Refrigerant leak checks and EPA rules

  • Which rule applies. EPA’s Section 608 leak repair rule covers appliances with 50 or more pounds of ozone-depleting refrigerant. Its AIM Act rule, in force since January 1, 2026, covers appliances with 15 or more pounds of an HFC or a substitute with a GWP above 53. Residential and light commercial A/C is excluded.

  • The trigger. EPA lists chillers as comfort cooling, with a 10% leak rate over 12 months. Industrial process refrigeration is 30%.

  • Chillers are covered. EPA’s fact sheet says chillers fall under their own subsector, not the excluded residential and light commercial group.

  • The clock. Repair within 30 days (120 if an industrial process shutdown is required), then run initial and follow-up verification tests. Repairs must be done by a certified technician.

  • The math. Calculate the leak rate every time refrigerant is added. Under the AIM Act, comfort cooling chillers over the rate need a leak inspection once a year until a year passes without exceeding it.

  • If you will not repair. A retrofit or retirement plan is due within 30 days, to be finished within a year, and records are kept for three years.

  • Read the rule itself. EPA’s pages say to consult 40 CFR Part 82 Subpart F and 40 CFR 84.106. This is not legal advice.

Condenser tube cleaning and eddy current testing

York says to clean the condenser tubes annually, or earlier if conditions warrant, and gives eddy current testing at 2 to 5 years. Daikin gives 5 years. York’s guide says to brush-clean before any acid cleaning, never to use a steel bristle brush, and that acid cleaning must be done by an expert. York says evaporator tubes do not normally need cleaning, and Daikin says evaporators in treated closed circuits are not normally subject to fouling.

Where the chiller sources disagree

York puts the full leak check monthly, Daikin and the DOE guide weekly. York flags fouling at 4 F above the new-unit approach, Daikin at 2 F. The DOE guide says to inspect the chiller as the manufacturer recommends, typically at least quarterly. The daily item uses York’s 4 F; the monthly calculation uses Daikin’s 2 F. Carrier, Trane and other makes have their own schedules, which we did not read.

What to do when a chiller check fails

  • Safety control fails or oil is low: stop and lock out. Check the oil return system and filter drier before restarting.

  • Isolate before service. OSHA 29 CFR 1910.147 requires isolating the chiller and verifying isolation first.

  • Refrigerant loss: a certified technician finds and repairs the leak. Record the amount added.

  • Write the reading on the checklist, tell the maintenance lead and open a work order. See the work order template.

Chiller maintenance mistakes

  1. No baseline. Without the new-unit approach, a rising number means nothing.

  2. No refrigerant record. Leak rate depends on knowing what was added.

  3. Untested safety controls. They only matter on the day they trip.

  4. Cleaning only when it fails. Annual cleaning is the York interval.

  5. Logs kept but never read. Review the weekly trend.

Keeping the chiller log on schedule

Morsa asks the operator for the daily log reading by phone, in WhatsApp, Teams, text or email, and files it against the chiller. It compares condenser approach with the baseline you set and tells the maintenance lead when it drifts. Refrigerant additions are logged as they happen and the leak rate is kept current, and weekly, monthly and annual tasks are scheduled for approval.

Other maintenance checklists

Frequently asked questions

How often should a chiller be serviced?

Log daily, check refrigerant and oil weekly, safety controls and leaks monthly, clean the condenser tubes yearly. The DOE guide adds a manufacturer inspection at least quarterly.

What is on a commercial chiller maintenance checklist?

Logs, oil, refrigerant, leaks, approach, safety controls, starter, tube cleaning, oil analysis, vibration and eddy current testing.

What is a York chiller maintenance schedule?

Johnson Controls lists daily, weekly, monthly and yearly items plus eddy current testing every 2 to 5 years. The checklist follows it.

How often should a chiller be checked for refrigerant leaks?

York says monthly, Daikin and DOE weekly. EPA’s rules set a 10% leak rate for comfort cooling chillers and require repair within 30 days.

How often should chiller tubes be cleaned?

Condenser tubes yearly, or sooner if approach rises 5 to 6 F over the new-unit value (York). Evaporator tubes rarely need it.

What is eddy current testing on a chiller?

A test of the tube walls to measure thickness. York recommends it every 2 to 5 years.

Where Morsa fits

Never miss a chiller reading or a leak record.

Morsa asks for the log, compares approach with your baseline and flags drift or a missed check. It works in whatever your plant runs on: WhatsApp, Teams, email or text.

Machines, people, and vendors, finally in one. We start with yours.

For queries, feedback or suggestions

© 2026 Morsa. All Rights Reserved. A Product by Lunar.

Machines, people, and vendors, finally in one. We start with yours.

For queries, feedback or suggestions

© 2026 Morsa. All Rights Reserved. A Product by Lunar.

Machines, people, and vendors, finally in one. We start with yours.

For queries, feedback or suggestions

© 2026 Morsa. All Rights Reserved. A Product by Lunar.