Commercial HVAC maintenance checklist
Every month, check filters, drain pans and the overflow switch, and read the alarm log. Every 3 months, stroke the dampers and inspect the fans. Twice a year, in spring and fall, inspect the coils and clean them if dirty, tighten the terminals and log the refrigerant pressures. Every year, clean the coils, review the balance report and record refrigerant added. Fill in the checklist below, then download it as a PDF (filled or blank) or an Excel file. Morsa asks for each check and flags a missed or failed one.
Updated November 12, 2026
Commercial HVAC preventive maintenance schedule at a glance
| How often | What to check | Source |
|---|---|---|
| Monthly | Filters, drain pans, overflow switch, belts, intakes, alarm log, humidity | ASHRAE, Trane, DOE |
| Every 3 months | Dampers and economizer, fans, air handler interior, sensors | ASHRAE |
| Spring and fall | Coils, bearings, terminals, refrigerant log, bird screens, drain pan treatment | Trane, ASHRAE |
| Yearly | Coil cleaning, balance report, sensor calibration, refrigerant leak rate | Trane, ASHRAE, EPA |
Frequencies follow ASHRAE’s preventive maintenance checklist (aligned to Standards 62.1 and 180, which we did not read themselves) and the Trane Precedent rooftop manual, which covers 3 to 25 ton packaged rooftop units.
How to use the commercial HVAC maintenance checklist
Enter the unit number and where it is.
Pick the checklist that is due and mark each check Done, Issue or N/A. Filters, drains, dampers, terminals and refrigerant log cannot be marked N/A. Belt, economizer and heating items are N/A when the unit has none.
Write the readings and what is wrong against failed items.
Download the PDF (filled or blank) or the Excel file for the maintenance log.
Rooftop unit and air handler maintenance: what the maker says
Trane’s rooftop unit manual (July 2026) lists filter inspection monthly, a cooling-season checklist and a heating-season checklist, and says regular coil maintenance, “including annual cleaning”, improves efficiency. For microchannel condenser coils it says not to use detergents and to use pressurized water or air at no more than 600 psi. During the cooling-season check, it says to log ambient temperature, suction and discharge pressure and superheat for each circuit. Your unit’s manual may differ.
Filters, drains, humidity and the ASHRAE checklist
ASHRAE’s checklist makes filter pressure drop and drain pans monthly items: replace a filter that exceeds the maximum pressure drop in the O&M manual, and check drain pans for standing water, growth or sediment. It sets space humidity at roughly 30 to 60% RH and says to investigate persistent readings above 60%. Quarterly it adds damper stroke tests and fan belt checks, and twice a year it adds bird screens, drain pan treatment and coil inspection.
HVAC refrigerant leak rules: EPA Section 608 and the AIM Act
Section 608 covers appliances with 50 or more pounds of ozone-depleting refrigerant. EPA lists chillers, commercial split systems and packaged rooftop units as comfort cooling, with a 10% leak rate over 12 months and repair within 30 days.
The AIM Act rule applies from January 1, 2026 to appliances with 15 or more pounds of an HFC or a substitute with a GWP above 53, with the same 10% rate for comfort cooling. Residential and light commercial air conditioning and heat pumps are excluded; EPA describes that group as equipment for individual rooms, single-family homes and small commercial buildings. Read the refrigerant charge on each unit’s nameplate: under 15 lb is outside this rule, and larger units need a check against EPA’s categories.
What to do now. Log every refrigerant addition. EPA says to calculate the leak rate each time refrigerant is added. A certified technician must do the repair.
Commercial HVAC maintenance contract or agreement: what to ask for
Scope by checklist. Ask which of these checklists the contractor does, and which your own staff do (monthly filters, drains, alarm review).
Visits. Spring cooling and fall heating are the two the Trane manual separates. Ask how many visits are included.
Records. Ask for the completed checklist after every visit, with readings.
Refrigerant. Ask who calculates the leak rate and keeps the EPA records.
Parts and response. Ask what is covered. We found no source for standard prices, so we do not give any.
Where the commercial HVAC sources disagree
ASHRAE’s checklist puts coil cleanliness checks on a 6-month and deep cleaning on a yearly cycle, and Trane says annual coil cleaning. Trane lists filters monthly and your plant’s dust may need weekly. DOE’s fans checklist lists belts monthly; ASHRAE puts belt wear on a quarterly list. We used the shorter interval for filters and belts, and the manual wins.
What to do when a commercial HVAC check fails
Isolate before service. Trane says to turn the unit off and lock the main disconnect open. OSHA 29 CFR 1910.147 requires lockout and verification.
Blocked drain or overflow switch stuck: fix before the next cooling run; water damage is the costly failure.
Low pressures or suspected leak: a certified technician finds and repairs it; do not vent refrigerant.
Write the fault and reading on the checklist and open a work order. See the work order template.
Commercial HVAC maintenance mistakes
Changing filters by calendar only. Read the pressure drop.
Ignoring the drain pan. Standing water grows things and floods ceilings.
No refrigerant record. The leak rate depends on knowing what was added.
Pressure-washing microchannel coils with detergent. The maker says not to.
No record of the visit. Ask the contractor for the checklist.
Keeping the HVAC checklist on schedule
Morsa sends the monthly checks to your building engineer or contractor in WhatsApp, Teams, text or email, files each unit’s readings and flags a missed filter or drain check. It keeps a refrigerant addition log per unit and the leak rate current, and schedules the spring and fall visits and the yearly coil cleaning for the maintenance lead to approve.
Other maintenance checklists
Preventive maintenance checklist: the hub, a general PM checklist for any machine
Chiller maintenance checklist: the central plant behind the air handlers
Cooling tower maintenance checklist: water treatment and Legionella
Boiler maintenance checklist: steam and hot water
Air compressor maintenance checklist: drains, filters and safety valves
Frequently asked questions
What should be on a commercial HVAC maintenance checklist?
Filters, drain pans, coils, belts, dampers and economizer, fans, sensors, electrical connections, refrigerant log and controls, each with a frequency.
How often should commercial HVAC be serviced?
Monthly checks on filters and drains, quarterly damper and fan checks, and spring and fall service. Yearly coil cleaning and a refrigerant leak review.
Is there an HVAC preventive maintenance checklist for rooftop units?
Yes. The checklists above follow Trane’s rooftop unit manual and ASHRAE’s preventive maintenance checklist.
What is a commercial HVAC maintenance agreement?
A contract for scheduled service. Ask for scope by checklist, number of visits, records of each visit and who handles refrigerant leak records.
What does ASHRAE say about HVAC maintenance?
ASHRAE’s checklist, aligned to Standards 62.1 and 180, sets monthly, quarterly, semiannual and annual tasks. We could not read the standards.
Do commercial HVAC units fall under the EPA leak repair rules?
Chillers and rooftop units are comfort cooling, but only if they are over the charge threshold: Section 608 applies at 50 lb of ozone-depleting refrigerant, the AIM Act at 15 lb of HFC, and light commercial units are excluded.
Related tools
Sources
ASHRAE, IAQ Preventive Maintenance Checklist (read November 12, 2026)
US DOE FEMP, O&M Best Practices Guide, Release 3.0 (read November 12, 2026)
EPA, Stationary refrigeration leak repair requirements (read November 12, 2026)
OSHA, 29 CFR 1910.147, The control of hazardous energy, osha.gov (read November 12, 2026)