Free tool
Boiler maintenance checklist
On a commercial or industrial steam boiler, check the water level and blow down the water column every day, blow down the boiler at least once every 8 hours, test the low water cutoff monthly, and check the safety valves and waterside surfaces every year. Your insurer and local law also require periodic inspection by an authorized inspector; ask yours how often. Fill in the checklist below, then download it as a PDF (filled or blank) or an Excel file. Morsa asks for the log and flags a missed or failed check.
Updated November 12, 2026
Commercial boiler maintenance schedule at a glance
| How often | What to check | Source |
|---|---|---|
| Daily | Water level, water column and boiler blowdown, combustion, log readings, water treatment | Cleaver-Brooks |
| Weekly | Fuel valves, alarms, limit and safety controls, flue gas, relief valves | Cleaver-Brooks, DOE |
| Monthly | Burner, low water cutoff test, flame failure test, combustion analysis | Cleaver-Brooks, DOE |
| Every 6 months | Clean low water cutoffs, refractory, oil pump strainer and preheater | Cleaver-Brooks |
| Yearly | Fireside and waterside surfaces, safety valves | Cleaver-Brooks |
| As insurer and law require | Periodic pressure vessel inspection by an authorized inspector; ask how often | Cleaver-Brooks |
This is the Cleaver-Brooks schedule for its firetube boilers plus the US DOE guide. The manual for your boiler and your jurisdiction’s rules come first.
How to use the boiler maintenance checklist
Enter the boiler number and the burner hours.
Pick the checklist that is due and mark each check Done, Issue or N/A. Steam, hot water, oil and gas items are N/A when they do not apply. Water level, low water cutoff, flame and safety checks cannot be marked N/A.
Write the readings and what is wrong against failed items.
Download the PDF (filled or blank) for the boiler room, or the Excel file for the log.
Steam boiler water level, blowdown and low water cutoff
Cleaver-Brooks says most major boiler damage comes from low water or untreated water, so be sure of the water level and blow down the water column daily. It recommends blowing down a steam boiler at least once in every eight-hour period, with the frequency set by water quality, and prefers frequent short blows to rare long ones. For the low water cutoff on a steam boiler, check operation by stopping the water flow and letting the level fall; if the control does not cut off the burner at the proper level, repair or replace it at once. Do not adjust the cutoff point.
Hot water boilers cannot have their cutoffs blown down because the whole system is flooded. Cleaver-Brooks says to remove the operating mechanism at least annually and clean the float, moving parts and the bowl. A water meter on the make-up line shows losses.
Boiler combustion checks and tune-ups
The DOE guide lists flue gas composition weekly, with natural gas at 1.5% oxygen and 10% carbon dioxide, No. 2 oil at 2.0% and 11.5%, and No. 6 oil at 2.5% and 12.5%. These vary with the fuel, and your burner maker’s targets win. Cleaver-Brooks adds a combustion analysis monthly.
EPA’s area source boiler rule (40 CFR 63 subpart JJJJJJ) requires tune-ups every 2 years for coal-fired boilers under 10 MMBtu/hr, biomass boilers and oil-fired boilers over 5 MMBtu/hr, and every 5 years for seasonal, limited-use, small oil-fired and oxygen-trim boilers. Gas-fired boilers are not covered by that rule, but the maker’s schedule, your insurer, your state’s boiler rules and any inspector still apply; we did not read state rules. The tune-up includes measuring CO and oxygen before and after adjustments. Larger industrial sites may fall under other rules. Check with your environmental lead.
Pressure vessel inspection and safety valves
Cleaver-Brooks says insurance regulations and local laws require periodic inspection of the pressure vessel by an authorized inspector, usually scheduled in an off season, and the yearly safety valve check, fireside and waterside cleaning and inspection happen in the same window. It gives no interval for the inspection, so ask your inspector and insurer. We did not read ASME CSD-1 (controls and safety devices for automatically fired boilers) or the National Board Inspection Code themselves.
Boilers in food plants: steam that touches food
Where steam contacts food, 21 CFR 173.310(a) says boiler water additives may be used only if the amount is not in excess of that required for its functional purpose, and the compounds are made from the substances the section lists. Check your water treater’s products against it. We did not read other food-contact rules.
Where the boiler sources disagree
Cleaver-Brooks lists weekly and monthly control checks; the DOE guide has the low water cutoff test monthly. Cleaver-Brooks’s own steam boiler text says to test cutoffs frequently and blow down the water controls daily, so many plants test more often than monthly. The checklist uses the monthly cutoff test because it is the only interval either source states; the daily water column blowdown covers the gap, and your inspector or insurer may require more. Fireside cleaning is yearly in both. Your manual wins.
What to do when a boiler check fails
Low water cutoff or flame failure test fails: take the boiler out of service. Do not run it.
Isolate before work. OSHA 29 CFR 1910.147 requires isolation and verification before servicing. Fuel and electrical isolation both count.
Safety valve leaks or will not lift: recondition or replace; do not gag it.
Write the fault and reading on the checklist, tell the maintenance lead and open a work order. See the work order template.
Boiler maintenance mistakes
Adjusting the low water cutoff. Cleaver-Brooks says not to.
Skipping daily blowdowns. Sludge builds and the level control sticks.
No log. The log is how combustion drift and water losses show up.
Treating gas-fired as exempt from everything. The EPA rule skips gas, but your inspector does not.
Delaying the pressure vessel inspection. Insurers and local law require it.
Keeping the boiler log on schedule
Morsa asks the operator for the daily log readings and the water level and blowdown confirmations by phone, in WhatsApp, Teams, text or email, and files them against the boiler. It flags a missed blowdown, a monthly cutoff test that is overdue or a reading that drifts, and reminds the lead to book the inspector before the date lapses.
Other maintenance checklists
Preventive maintenance checklist: the hub, a general PM checklist for any machine
Chiller maintenance checklist: daily readings and annual service
Cooling tower maintenance checklist: water treatment and Legionella
Commercial HVAC maintenance checklist: rooftop units and air handlers
Plant shutdown checklist: phases from planning to restart
Frequently asked questions
What should be on a boiler maintenance checklist?
Water level and blowdown, combustion, controls and safety devices, the low water cutoff and flame failure tests, safety valves, and the annual inspection.
How often should a commercial boiler be serviced?
Daily and weekly checks by operators, monthly tests, a 6-month and a yearly service, and a pressure vessel inspection as your jurisdiction requires.
How often should a steam boiler be blown down?
Cleaver-Brooks recommends at least once in every eight-hour period, with the water column blown down daily. Your water treater sets the frequency.
How often should a low water cutoff be tested?
Cleaver-Brooks says to check frequently and blow down the water controls on a steam boiler daily. The DOE guide lists a monthly test.
What is steam boiler maintenance?
Daily water level, blowdown and logs; weekly control checks; monthly tests; yearly cleaning, inspection and safety valve checks.
Does a boiler need a tune-up by law?
EPA’s area source rule requires 2 or 5-year tune-ups for some coal, biomass and oil boilers. Gas-fired boilers are not covered by it.
Related tools
Sources
Cleaver-Brooks, CBEX Elite 1300-2200 Operation and Maintenance Guide (read November 12, 2026)
Cleaver-Brooks, CBEX-DE manual, periodic inspection (read November 12, 2026)
US DOE FEMP, O&M Best Practices Guide, Release 3.0 (read November 12, 2026)
EPA, Small entity compliance guide for area source boilers (read November 12, 2026)
OSHA, 29 CFR 1910.147, The control of hazardous energy, osha.gov (read November 12, 2026)
FDA, 21 CFR 173.310, Boiler water additives, eCFR (read November 12, 2026)
Where Morsa fits
Keep every blowdown, test and inspection on the calendar.
Morsa asks for the daily log, files it against the boiler and flags a missed test or a drifting reading. It works in whatever your plant runs on: WhatsApp, Teams, email or text.